Bryant 564A Manuale Utente

Navigare online o scaricare Manuale Utente per Condizionatori Bryant 564A. Bryant 564A User Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 20
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
NOTE: Read the entire instruction manual before starting the
installation.
Index Page
SAFETY CONSIDERATIONS .....................................................1
RULES FOR SAFE INSTALLATION
AND OPERATION........................................................................1
GENERAL ................................................................................1
RECEIVING AND INSTALLATION.......................................5-8
Check Equipment ...........................................................................5
IDENTIFY UNIT......................................................................5
INSPECT SHIPMENT .............................................................5
Provide Unit Support .....................................................................5
SLAB MOUNT.........................................................................5
Provide Clearances.........................................................................5
Place Unit .......................................................................................5
Select and Install Ductwork .......................................................5-6
INSTALL FLANGES FOR DUCTWORK
CONNECTIONS (060 Only) ...................................................5
CONVERTING HORIZONTAL DISCHARGE UNITS
TO DOWNFLOW (Vertical) DISCHARGE ...........................6
Provide for Condensate Disposal ..................................................6
Install Electrical Connections.....................................................6-8
HIGH-VOLTAGE CONNECTIONS .......................................7
ROUTING POWER LEADS INTO UNIT..............................8
CONNECTING GROUND LEAD TO UNIT GROUND ......8
ROUTING CONTROL POWER WIRES................................8
ACCESSORY ELECTRIC HEAT WIRING...........................8
SPECIAL PROCEDURES FOR 208-V OPERATION...........8
PRE-START-UP .........................................................................8-9
START-UP................................................................................9-14
MAINTENANCE....................................................................14-16
TROUBLESHOOTING ...............................................................17
START-UP CHECKLIST............................................................18
NOTE TO INSTALLER — Before the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY. Also,
make sure the User’s Manual and Replacement Guide are left with
the unit after installation.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified workers should install, repair, or service
air-conditioning equipment.
Untrained workers can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
by trained service people. When working on air-conditioning
equipment, pay attention to precautions in the literature, tags and
labels attached to the unit, and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
WARNING: Before performing service or maintenance
operations on system, turn off main power to unit. Turn
off accessory heater power switch if applicable. Electrical
shock can cause serious injury or death.
RULES FOR SAFE INSTALLATION AND OPERATION
Recognize safety information. This is the safety-alert symbol
.
When you see this symbol in instructions or manuals, be alert to
the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen-
tial construction practices. We require these instructions as a
minimum for a safe installation.
A. General
564A cooling units are fully self-contained and designed for
outdoor installation. See Fig. 1. As shown in Fig. 2-4, units are
shipped in a horizontal-discharge configuration for installation on
a ground-level slab. All units can be field-converted to downflow
discharge configurations for rooftop applications with a field-
supplied plenum.
Fig. 1—Unit 564A (Size 036 Shown)
C00001
installation, start-up
and service instructions
3-PHASE
PACKAGED AIR CONDITIONERS
Cancels: New II 564A-36-1
1-06
564A
036-060
—1—
Vedere la pagina 0
1 2 3 4 5 6 ... 19 20

Sommario

Pagina 1 - PACKAGED AIR CONDITIONERS

NOTE: Read the entire instruction manual before starting theinstallation.Index PageSAFETY CONSIDERATIONS ...

Pagina 2 - NEC. REQUIRED CLEARANCES

2. Refer to appropriate chart to determine what the suctiontemperature should be.3. If suction temperature is high, add refrigerant. If suctiontempera

Pagina 3

A06023Fig. 15—208/230-3-60 Wiring Diagram—11—

Pagina 4

A06024Fig. 16—460-3-60 Wiring Diagram—12—

Pagina 5

B. For 460-v MotorsThe motor leads are color coded as follows:3-SPEED (060 ONLY) 2-SPEEDblack = high speed black = to purple- yellow = lineorange = me

Pagina 6 - HERE FOR SHIPMENT

TABLE 3—ELECTRICAL DATAUNIT 564ASIZEV-PH-HZVOLTAGERANGECOMPRESSOR OFM IFM ELECTRIC HEAT POWER SUPPLY DISCONNECT SIZEMin Max RLA LRA FLA FLA Nominal kW

Pagina 7 - 1200 1225 1400 1750

through the overload with an ohmmeter or continuity tester.VI. SEQUENCE OF OPERATIONA. FAN OPERATIONThe FAN switch on the thermostat controls indoor f

Pagina 8

2. Inspect indoor coil, outdoor coil, drain pan, and condensatedrain each cooling season for cleanliness. Clean whennecessary.3. Inspect blower motor

Pagina 9

c. Reassemble blower into housing. Place upper orifice ringon blower to judge location of the blower wheel. Blowerwheel should be approximately 0.2-in

Pagina 10

TABLE 8 — TROUBLESHOOTING — COOLINGSYMPTOM CAUSE REMEDYCompressor and condenser fan will not start.Power failure Call power company.Fuse blown or circ

Pagina 11

START-UP CHECKLIST (REMOVE AND STORE IN JOB FILE)I. PRELIMINARY INFORMATIONModel No. ...

Pagina 12

UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHTCENTER OF GRAVITYIN. [MM]lb kg X Y Z036 208/230-3-60 250 114 355.6 (14.00) 508.0 (20.00) 241.3 (9.50)Fig. 2—

Pagina 13 - - yellow = line

© 2006 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231—20—Printed in U.S.A. Catalog No. II 564A-36-1

Pagina 14 - TABLE 3—ELECTRICAL DATA

UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHTCENTER OF GRAVITYIN. [MM]lb kg X Y Z042 208/230-3-60 297 135 355.6 (14.00) 508.0 (20.00) 304.8 (12.00)048 20

Pagina 15

UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHTCENTER OF GRAVITYIN. [MM]lb kg X Y Z060 208/230-3-60, 460-3-60 350 159 355.6 (14.00) 508.0 (20.00) 355.6 (14

Pagina 16

RECEIVING AND INSTALLATIONI. CHECK EQUIPMENTA. Identify UnitThe unit model number and serial number are stamped on the unitidentification plate. Check

Pagina 17 - 3.125 in

B. CONVERTING HORIZONTAL DISCHARGE UNITS TODOWNFLOW (Vertical) DISCHARGEWARNING: Before performing service or maintenanceoperations on system, turn of

Pagina 18

CAUTION: Failure to follow these precautions couldresult in damage to the unit being installed:1. Make all electrical connections in accordance withNE

Pagina 19

fuse/circuit breaker size and minimum circuit amps (ampacity) forwire sizing. See Table 3 for electrical data.The field-supplied disconnect may be mou

Pagina 20

erant leak. Leak-test all refrigerant tubing connectionsusing electronic leak detector, or liquid-soap solution. Ifa refrigerant leak is detected, see

Commenti su questo manuale

Nessun commento