NOTE: Read the entire instruction manual before starting theinstallation.Index PageSAFETY CONSIDERATIONS ...
2. Refer to appropriate chart to determine what the suctiontemperature should be.3. If suction temperature is high, add refrigerant. If suctiontempera
A06023Fig. 15—208/230-3-60 Wiring Diagram—11—
A06024Fig. 16—460-3-60 Wiring Diagram—12—
B. For 460-v MotorsThe motor leads are color coded as follows:3-SPEED (060 ONLY) 2-SPEEDblack = high speed black = to purple- yellow = lineorange = me
TABLE 3—ELECTRICAL DATAUNIT 564ASIZEV-PH-HZVOLTAGERANGECOMPRESSOR OFM IFM ELECTRIC HEAT POWER SUPPLY DISCONNECT SIZEMin Max RLA LRA FLA FLA Nominal kW
through the overload with an ohmmeter or continuity tester.VI. SEQUENCE OF OPERATIONA. FAN OPERATIONThe FAN switch on the thermostat controls indoor f
2. Inspect indoor coil, outdoor coil, drain pan, and condensatedrain each cooling season for cleanliness. Clean whennecessary.3. Inspect blower motor
c. Reassemble blower into housing. Place upper orifice ringon blower to judge location of the blower wheel. Blowerwheel should be approximately 0.2-in
TABLE 8 — TROUBLESHOOTING — COOLINGSYMPTOM CAUSE REMEDYCompressor and condenser fan will not start.Power failure Call power company.Fuse blown or circ
START-UP CHECKLIST (REMOVE AND STORE IN JOB FILE)I. PRELIMINARY INFORMATIONModel No. ...
UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHTCENTER OF GRAVITYIN. [MM]lb kg X Y Z036 208/230-3-60 250 114 355.6 (14.00) 508.0 (20.00) 241.3 (9.50)Fig. 2—
© 2006 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231—20—Printed in U.S.A. Catalog No. II 564A-36-1
UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHTCENTER OF GRAVITYIN. [MM]lb kg X Y Z042 208/230-3-60 297 135 355.6 (14.00) 508.0 (20.00) 304.8 (12.00)048 20
UNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHTCENTER OF GRAVITYIN. [MM]lb kg X Y Z060 208/230-3-60, 460-3-60 350 159 355.6 (14.00) 508.0 (20.00) 355.6 (14
RECEIVING AND INSTALLATIONI. CHECK EQUIPMENTA. Identify UnitThe unit model number and serial number are stamped on the unitidentification plate. Check
B. CONVERTING HORIZONTAL DISCHARGE UNITS TODOWNFLOW (Vertical) DISCHARGEWARNING: Before performing service or maintenanceoperations on system, turn of
CAUTION: Failure to follow these precautions couldresult in damage to the unit being installed:1. Make all electrical connections in accordance withNE
fuse/circuit breaker size and minimum circuit amps (ampacity) forwire sizing. See Table 3 for electrical data.The field-supplied disconnect may be mou
erant leak. Leak-test all refrigerant tubing connectionsusing electronic leak detector, or liquid-soap solution. Ifa refrigerant leak is detected, see